Working principle of gas solenoid valve
1、 Working principle of direct acting gas solenoid valve
Direct acting gas solenoid valve is the same as ordinary solenoid valve. When the solenoid coil is powered on, the electromagnetic force lifts the seal from the valve seat, and the valve will open. When the solenoid valve coil is powered off, the electromagnetic force disappears, and the seal will return to its original position.
2、 Working principle of pilot operated gas solenoid valve
When the pilot type gas solenoid valve is powered on, the pressure in the upper chamber drops rapidly, the upper low and high pressure difference is formed around the closure, the fluid pressure pushes the closure upward, and the valve opens; In case of power failure, the spring force closes the pilot hole, the inlet pressure forms a pressure difference between lower and upper around the valve closing part through the bypass hole chamber, and the fluid pressure pushes the closing part to move downward to close the valve.
3、 Working principle of urban gas solenoid valve
When the normal ventilation solenoid head of the urban gas solenoid valve is energized, the valve rod will be locked by the solenoid head, and the valve is open at this time. When the gas pipeline or gas equipment leaks and the mixed concentration of gas and air reaches 25% of the lower limit of explosion limit, the detector sends a signal to the controller. The controller sends an audible and visual alarm and starts the exhaust fan. At the same time, cut off the current 220V solenoid head to control the voltage and drive the electromagnet to release the valve rod of the safety valve. The valve rod falls rapidly under the action of spring and self weight, Close the valve port and cut off the air supply. After power failure, the shut-off valve cannot be opened manually due to self-locking.
4、 Working principle of distributed direct acting gas solenoid valve
After the distributed direct acting gas solenoid valve is energized, the electromagnetic force directly lifts the pilot small valve and the main valve closure up in turn, and the valve opens. When the inlet and outlet reach the starting pressure difference, after power on, the electromagnetic force pilot small valve, the pressure in the lower chamber of the main valve increases and the pressure in the upper chamber decreases, so as to push the main valve upward by using the pressure difference; In case of power failure, the pilot valve uses the spring force or medium pressure to push the closure and move downward to close the valve.