Knowledge

How to install the temperature-sensitive cable and the precautions

Feb 05, 2020 Leave a message

How to install the temperature-sensitive cable and the precautions

Temperature cable can be widely used in industrial warehouses, plants and other places, according to the characteristics of the protection of the object of fire can choose the roof installation or wall installation.

Temperature-sensitive cables are generally installed and routed to positive "S"-shaped wiring.


Temperature cables are installed on the roof of the plant or warehouse, or not greater than 0.5m from the side wall (generally preferred within 0.2m to 0.3m), which can form a protective area in the building.


Temperature-sensitive cables should be laid in the form of parallel suspension, the distance between parallel lines should not exceed 4m. The distance between the temperature cable and the ground is 3m and should not exceed 9m. When the distance from the ground is greater than 3m, the distance between the temperature cables should be reduced according to the situation. Where installation conditions permit, it is recommended that the temperature-sensitive cable be installed close to the flammable area, so that the installation of the detector has an advantage, the detector can respond quickly to the fire. Humidity Sensor Probe, Stainless Steel Electric Tube PT100 Sensor, Cast Aluminum Heater, Heating Ring Fluid Soleid Valve


If the temperature-sensitive cable is placed in a corridor, such as a long strip of buildings such as aisles, it is advisable to use a line in the middle of the arrangement. The suspension line should have a tightening device, every 2m with a fixed caliper to secure the cable to the suspension line.


When applied in the shelf, the temperature-sensitive cable can be installed under the ceiling, arranged along the centerline of the shelf aisle, or can be attached together with the water-spraying fire extinguishing system pipe, while the temperature-sensitive cable is fixed in the vertical ventilation space. When there are more dangerous items in the shelf, the temperature cable should be installed in each shelf, but can not affect the normal work of the shelf, so as not to access the goods to damage the temperature-sensitive cable. The height is greater than 4.5m shelves, in order to better detect low-level fire, it is necessary to add a layer of temperature-sensitive cable in the direction of height, if there is a sprinkler system can be unified with the sprinkler layer.


Send Inquiry